72 Software index Emotron AB 01-3990-11r3
10- Volt/Hz Operation Mode
Function
Code no.
Description Range/Code
Factory
setting
Re-
marks
10-0 Volts/Hz Patterns 0 to 18 0/9 *4*6
10-1
Volts/Hz Curve Modification
(Torque Boost) (%)
0 to 30.0 0.0 *1*6
10-2
Motor No Load Current
(Amps AC)
----- *5*6
10-3 Motor Slip Compensation (%) 0.0 to 100.0 0.0 *1*6
10-4 Maximum Frequency (Hz) 0.20 to 650.00
50.00/
60.00
*4*6
10-5
Maximum Frequency Voltage Ratio
(%)
0.0 to 100.0 100.0 *6
10-6 Mid Frequency (Hz) 0.10 to 650.00
25.00/
30.00
*4*6
10-7 Mid Frequency Voltage Ratio (%) 0.0 to 100.0 50.0 *6 *7
10-8 Minimum Frequency (Hz) 0.10 to 650.00
0.50/
0.60
*6
10-9
Minimum Frequency Voltage Ratio
(%)
0.0 to 100.0 1.0 *6 *7