EasyManuals Logo

Emotron VSC Series User Manual

Emotron VSC Series
Go to English
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #75 background imageLoading...
Page #75 background image
74 Software index Emotron AB 01-3990-11r3
12- PID "Limits" and "Out of Range" Mode
Function
Code no.
Description Range/Code
Factory
setting
Re-
marks
12-0
Feedback Loss
Detection Mode
0000: Disabled
0001: Enabled - Drive
Continues to Operate After
Feedback Loss
0002: Enabled - Drive
"STOPS" After Feedback Loss
0000
12-1
Feedback Loss
Detection Level (%)
0 to 100 0
12-2
Feedback Loss
Detection Delay Time
(Seconds)
0.0 to 25.5 1.0
12-3
Integration Limit Value
(%)
0 to 109 100 *1
12-4
Integration Value
Resets to Zero when
Feedback Signal
Equals the Intended
Value
0000: Disabled
0001: 1 s
0030: 30 s
0000
12-5
Allowable Integration
Error Margin (Units)
(1 Unit = 1/8192)
0 to 100 0
12-6 PID Feedback signal
0000: 0–10 V or 0–20 mA
0001: 2–10 V or 4–20 mA
0000 *7
12-7
Sleep Function
Operation Level
0.00 to 650.00 0.0
12-8
Sleep Function Delay
Time
0.0 to 25.5 0.0

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emotron VSC Series and is the answer not in the manual?

Emotron VSC Series Specifications

General IconGeneral
BrandEmotron
ModelVSC Series
CategoryInverter
LanguageEnglish