Emotron AB 01-3990-11r3 Software index 75
13- Communication Mode
14- Motor Autotune Parameters
Function
Code no.
Description Range/Code
Factory
setting
Re-
marks
13-0
Assigned Commu-
nication Station
Number
1 to 254 1 *2*3
13-1
Baud Rate Setting
(bps)
0000: 4800
0001: 9600
0002: 19200
0003: 38400
0003 *2*3
13-2 Stop Bit Selection
0000: 1 Stop Bit
0001: 2 Stop Bits
0000 *2*3
13-3 Parity Selection
0000: Without Parity
0001: With Even Parity
0002: With Odd Parity
0000 *2*3
13-4
Data Format Selec-
tion
0000: 8-Bits Data
0001: 7-Bits Data
0000 *2*3
13-5
Communication
time-out operation
selection
0000: Deceleration to stop
According Deceleration time 1
(3-03)
0001: Coast to stop
0002: Deceleration to stop
According Deceleration time 2
(3-07)
0003: continue operation
0000
13-6
Communication
time-out detection
time
00.0 to 25.5 Sec 00.00 *11
Function
Code no.
Description Range/Code
Factory
setting
Re-
marks
14-0 Stator Resistance (Ohms) ----- *3*5
14-1 Rotor Resistance (Ohms) ----- *3*5
14-2 Equivalent Inductance (mH) ----- *3*5