11. Step By Step Software Configuration:
Note: it is assumed that all installation procedures are complete.
Firstly, insert the Key into the Panel’s Control Keyswitch, located at the right of the
Panel. Turn the Key to the “ON” Position.
Step Action Screen Display
No
1 Press the “0” key followed by the “” button until the
screen displays:
2 Press the “YES” key and the screen will now display:
3 Press the “” button until the screen displays:
4 Press the “YES” key and the screen will
now display:
5 Enter 221100 then press the “YES” key and the
screen will now display:
6 Press the “” button until the screen displays:
7 Press the “YES” key followed “0” key on the Keypad
the screen will now display:
8 Press the “” button until the screen displays:
9 Press the “YES” key. The screen will now display:
| ** Fire system ** |
>Dev. Disable/Test<
| Net. Disable/Test |
Yes= Select Time
| System Mode |
>Engineers Config <
| Printer Options |
Yes= Select Time
Enter Your PIN
For Access>
Then Press YES
Time
| ** Eng.; Config ** |
> Device Database <
| Sounder Options |
Yes= Select Time
| Reset Security |
> Reset System <
| LAN Options |
Yes= Select Time
|** Main Menu ** |
> Pins & Access <
| System Support |
Yes= Select Time
| System Support |
> Serial Comms <
| Pager Setup |
Yes= Select Time
|* Serial Comms *|
> Device Table <
| Re-start bus |
Yes= Select Time
| Logging |
>Fire System Opts <
| Remote Access |
Yes = select Time