Checking background interference levels
Access the Main Menu by following the operations listed under the previous Accessing the
engineering menus section.
The Iris+ should now be set up to Monitor Background Signals as their presence at a high level
may eect the performance of the system. To enter this mode from the Main Menu select;
Radio Setup > Test Routines > Monitor Carrier.
Monitoring Carrier
Level = 26
Highest = 27
13:35
Page 8 of 32
*Test Menu*
Monitor Signal
Min/Max Report
Call-In Report
Battery Report
Monitor Carrier
*Radio Setup*
Add Transmitter
Transmitter Details
Replace Transmitter
Suspend Transmitter
Reinstate Transmitter
Test Routines
Delete Transmitter
*Main Menu*
PINs & Access
System Support
Serial Comms
Pager Setup
Engineer Ctrl
Time & Date
Radio Setup
Output Setup
Logging
Relay Setup
Remote Rxers
Direct Inputs
Network
Txer Grouping
Bus I/O
With Iris+ in Monitor Carrier mode the screen will show any background signals on and around
the frequency at which Iris operates. A typical screen shot is shown below. NOTE: Background
signals are generated by other electronic equipment such as computers, Fax machines, mobile
phones, surveillance cameras.
An acceptable level of background noise is between 0 and 55. Any higher indication may
adversely eect the performance of the system. If the level is shown to be high, there are a
number of steps that can be taken to reduce the reading, these are outlined overleaf.