Micropilot FMR51, FMR52 PROFIBUS PA Installation
Endress+Hauser 29
7. Tighten the securing clamp again using the Allen key (Torque: 2.5 Nm).
6.10 Post-installation check
m
Is the device undamaged (visual inspection)?
m
Does the device conform to the measuring point specifications?
For example:
Process temperature
Process pressure (refer to the chapter on "Material load curves" of the "Technical Information"
document)
Ambient temperature range
Measuring range
m
Are the measuring point identification and labeling correct (visual inspection)?
m
Is the device adequately protected from precipitation and direct sunlight?
m
Are the securing screw and securing clamp tightened securely?