BA1027N/08/en/11.08
70105589
Valid as of Software-Version:1.40
Operating Instructions
Oil Leak Detector NAR 300 System

Questions and Answers

  • R
    Rebecca MaloneAug 11, 2025
    What to do if the Endress+Hauser Security Sensors LED is red but there is no voltage?
    • K
      Kayla DavisAug 11, 2025
      If the voltage for the sensor isn't detected but the alarm is still triggered, and there are no wiring issues between the transmitter and the Sensor I/F Ex box, then replace the transmitter.
  • S
    Scott LoganAug 16, 2025
    What to do if Endress+Hauser Security Sensors LED is not luminescent?
    • R
      romankathleenAug 16, 2025
      If the transmitter is powered off, and the regular voltage is measured between terminal L and N on the transmitter, replace the transmitter.
  • T
    tina43Aug 23, 2025
    What to do if Endress+Hauser NAR300-13 Security Sensors show voltage when the pit is empty?
    • J
      Judith AyalaAug 23, 2025
      If a false alarm is generated by the transmitter, please replace the transmitter.
  • G
    garrisonzacharyAug 29, 2025
    Why does my Endress+Hauser Security Sensors alarm go off when there is no oil leak?
    • A
      Abigail JordanAug 29, 2025
      Even if an oil leak doesn't occur, the alarm might be triggered if: the water in the pit freezes (the conductivity sensor will read it as an insulator), the float sensor tilts (reading air as an insulator), trash covers the conductivity sensor (detecting an insulator), the sensor is buried in dried mud (tuning-fork sensor reads it as liquid), snow covers the sensor (conductivity sensor detects an insulator), or the water in the pit has high resistance (conductivity sensor detects an insulator).
  • T
    Tammy HillSep 3, 2025
    Why doesn't my Endress+Hauser NAR300-13 alarm go off when there is an oil leak?
    • B
      baileyrobertsSep 3, 2025
      The alarm may not trigger even if an oil leak occurs if: wave and convection on liquid level, the float sensor is heavily tilted, the float sensor sinks, trash containing water exists, oil leak when it is snowing, gravity change of the water in pit.