EasyManua.ls Logo

Endress+Hauser nivotester FTL 325 P - Certificates and Approvals; Ordering Information

Endress+Hauser nivotester FTL 325 P
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
Certificates and approvals
CE mark The device meets the statutory requirements of EC directives.
Endress+Hauser confirms the successful testing of the device by affixing the CE mark.
Ex approval The Endress+Hauser sales office will provide you with information on the currently suppliable
Ex versions (ATEX EEx ia; FM IS; CSA IS)
All data relevant for explosion protection can be found in separate Ex documentation
(see: Supplementary Documentation). This can be requested as necessary.
Protection type [EEx ia] IIC
Overspill protection WHG
External standards and
guidelines
Compliance with external standards and guidelines in the design and development of the
Nivotester FTL 325 P.
EN 60529
Type of ingress protection for housing (IP Code)
EN 61010
Safety specifications for electrical measurement, control and laboratory instruments
EN 61326
Interference emission (Class B apparatus), interference immunity (Appendix A - Industry)
IEC 61508
Functional safety of safety-relevant electrical/electronic/programmable electronic systems
(E/E/PES)
DIN V 19250
Fundamental Safety aspects for measurement and control equipment
Functional safety SIL1 / SIL2 / SIL3 or Ak 2...6 connected with FEL 57 for protection functions as overspill protection!
Ordering information
Nivotester FTL 325 P
10 Certificates
F ATEX II (1) GD [EEx ia] IIC, Overspill protection to WHG
H ATEX II (1) GD [EEx ia] IIC, Overspill protection to WHG, SIL2 (IEC 61508)
O FM IS Cl. I, II, III Div.1 Group A-G
P FM IS Cl. I, II, III Div.1 Group A-G, SIL2 (IEC 61508)
S CSA IS Cl. I, II, III Div.1 Group A-G
T CSA IS Cl. I, II, III Div.1 Group A-G, SIL2 (IEC 61508)
V * TIIS, Ex ia IIC
W * TIIS, Ex ia IIC, SIL2 (IEC 61508)
20 Version
1 Top-hat rail installation 1-channel 22.5 mm
3 Top-hat rail installation 3-channel 45 mm
9 Special design
30 Voltage supply
A Power supply 85... 253 V AC, 50/60 Hz
E Power supply 20... 30 V AC / 20... 60 V DC
Y Special design
40 Output
1 1x level SPDT + 1x alarm SPST
3 3x level SPDT + 1x alarm SPST
9 Special design
FTL 325 P Complete product designation