Installation
10
3 Installation
3.1 Incoming acceptance, transport, storage
3.1.1 Incoming acceptance
Check the packing and contents for any signs of damage.
Check the shipment, make sure nothing is missing and that the scope of supply matches your order.
3.1.2 Delivery content
• Tankvision
• Ferrite for installation on the power supply cable
• Operating Instruction BA340F/00
3.1.3 Transport, storage
Pack the measuring instrument so that it is protected against impacts for storage and transport. The
original packing material provides the optimum protection for this.
Permissible storage temperature: 0 to +55 °C (32°F to 131°F).
3.2 Mounting
3.2.1 Dimensions
NXA82xxx-06-00-00-yy-002
3.2.2 Installation conditions
• The DIN-rail housing must be mounted outside hazardous areas in a cabinet.
• The housing is mounted on a DIN rail EN 60715 TH 35x7,5 or TH 37x15.
• Do not install the instrument in the vicinity of high-voltage lines, motor lines, contactors or
frequency converters. The installation regulations for high-voltage lines, motor lines, contactors
or frequency converters must be observed.
• To ensure easy mounting and opening of the housing, a distance of approx. 1 cm (0.39 in) should
be kept between the instruments.
43 (1.7”)
35 (1.4”)
104 (4.1”)
150 (5.9”)
140 (5.5”)
100 (3.9)
Gap ≥ 50 (2”)
Gap ≥ 50 (2”)