Inspect battery shipment upon arrival for transit damage and verify contents against the packing slip.
Store batteries in a dry, clean, and cool location. Adhere to recommended storage intervals based on temperature.
Install in a clean, dry area. Avoid high temperatures and direct sunlight for optimal service life.
Ensure adequate ventilation, especially in cabinets, as batteries release gas during normal operation.
EnerSys® battery racks and cabinets are recommended for proper installation.
Perform a commissioning charge using a constant voltage charger at specific Vpc levels for 24 or 72 hours.
Maintain a float voltage of 2.27 Vpc at 77°F (25°C), adjusting for temperature variations.
An equalize charge can be performed at an elevated voltage of 2.40 Vpc for up to 16 hours.
Limit continuous ripple current to prevent damage and maintain service life, refer to Table 1.
Use current-limited, constant voltage charging. State of charge determined by open circuit voltage.
Limit the end of discharge voltage to a minimum of 1.60 Vpc to prevent deep discharge.
Immediately return discharged batteries to float recharge mode to avoid reduced service life.
Batteries are maintenance-free. Record individual voltages, resistance, and ambient temperature annually.