5.4 Default settings at the factory
On the LCD display you will find several of the UPS parameters to select. Default
settings are as follows:
Settings Selection Factory default
Output Voltage Setting
100/110/115/120/127
Vac
120V (FOR LV series)
208/220/230/240 Vac 230V (FOR HV series)
Input/Bypass Voltage
±10%
+10/-15%
+15/-20%
+10/-15%
Input/Frequency
±2%
±5%
±7%
±5%
HE Mode Setting On/Off Off
Free Run Mode On/Off On
Bypass Enable/Disable at free run mode Disable/Enable Disable
Alarm silence On/Off Off
Site wiring alarm Enable/Disable Disable
External Battery pack setting 0, 1, 2 0
You may change default settings, but we recommend that this is done after installation and before
starting up loads. Read UPS configurations in chapter 7.2 for more information.