32
7.5 Trouble shooting
Displayed on LCD Audible Alarm Alarm Description What You Should Do
Output Overload
Two Beeps per
second
The UPS is overloaded (in
Line Mode). Your
equipment needs more
power than the UPS can
provide. The UPS
Shut off the least important
equipment connected to the
UPS. If this solves the overload
problem, the UPS will switch
from bypass back to normal
Battery Test No Beeps
The UPS is doing a
battery test.
No action needed. The UPS will
return to normal operation when
it successfully completes the
battery test.
Over-Charge Constant beep Batteries are overcharged.
Turn off protected loads. Turn
off UPS and call your local
Low Battery
2 beeps every
5seconds
The unit is operating on
Battery Power and will
shut down soon due to
The unit will restart
Automatically when acceptable
power returns.
On-Battery
Once every 5
Save your data and perform a
Over-Temperature Constant beep
High ambient
Temperature.
Make sure the unit’s fans and
vent holes are not blocked, and
make sure the ambient
surrounding temperature is not
above 40 degree C. If these
conditions did not solve the
problem, call your service
Bus Fault
2 Beeps per
second
High internal DC bus
Voltage.
Turn off protected loads. Turn
off UPS and call your local
Site wiring Fault
1 Beep per
second
Voltage detected Between
Neutral and Ground
UPS mains connector polarity
Wrong. Rotate the connector
(Schuko). UPS installed to
mains supply without ground.
See page 15 on how to disable