EVR AUTOMATIC RECLOSER http://www.entecene.co.kr
31
ENHANCED TECHNOLOGY
The total length of the inter-connecting multi-core cable would be 6 meters as standard and the
longer cable is available upon request by client as option.
The fixing arrangement multi-core cable should be tightened by using tie band with every 1000
length against wind-waving.
To prevent pulling weight, loosen slighty the control cable between the cable connector and the
nearest hanger band.
5.3.3. Earthing
Figure 5-6 shows the earthing common to the recloser tank and the control cubicle.
To avoid the potential gradient differential among tank, control cubicle and surge arrester, Earthing
path should be common and do not ground by a different path to all equipments and be sure to keep
the ground cables away from the control cable by the maximum spacing available.
The earthing conductor size should be at least 60㎟.