Questions and Answers

  • Y
    Yolanda BarnesAug 12, 2025
    How to fix E101 non-locking fault on Envirovent energiSava 300 Fan?
    • C
      Christine FigueroaAug 12, 2025
      An E101 non-locking fault on your Envirovent Fan indicates a defective pressure sensor extract fan or blocked/kinked blue pressure hoses. In this state, the system switches to constant RPM control, and the preheater turns on when outdoor temperatures drop below 0°C. To address this: * Disconnect the unit from power. * Examine the blue pressure hoses (and pressure tubes) for fouling, kinking, or damage.
  • N
    Nancy JohnstonAug 19, 2025
    What causes E103 non-locking fault in Envirovent Fan?
    • B
      Billy PattersonAug 19, 2025
      The E103 non-locking fault in your Envirovent Fan indicates a bypass fault. This might be due to the current being too low (possibly from a stepper motor not correctly connected or effective) or too high (potentially from a short-circuit in the wiring or stepper motor). To resolve this: * Disconnect the unit from power. * Check the stepper motor connection, and replace the wiring or stepper motor if necessary.
  • V
    Victoria CastroAug 26, 2025
    What to do if Envirovent Fan displays E104 locking fault?
    • S
      Shelby FullerAug 26, 2025
      If your Envirovent Fan displays an E104 locking fault, it indicates the extract fan is defective. As a result, both fans and the preheater (and postheater, if applicable) will switch off, and the system will attempt a restart every 5 minutes. To resolve this: * Disconnect the unit from power. * Replace the extract fan. * Restore power to the appliance; the fault should automatically reset. * Check the cabling.
  • S
    sean40Sep 2, 2025
    Why does my Envirovent energiSava 300 Fan show E100 non-locking fault?
    • M
      matthew68Sep 2, 2025
      The Envirovent Fan displaying an E100 non-locking fault suggests a defective pressure sensor supply fan or blocked/kinked red pressure hoses. When this occurs, the system switches to constant RPM control, and the preheater activates at outdoor temperatures below 0°C. To troubleshoot: * Disconnect the unit from power. * Inspect the red pressure hoses (and pressure tubes) for any fouling, kinking, or damage.

Envirovent energiSava 300 Specifications