- Main control output max rate of rise - [r.E06]
This parameter is available when one control output is
configured as main output.
Ranges: from 0.1%/s to 25.0%/s.
Above this value the display shows “Inf” meaning that no limit is
imposed
NOTES:
1) This parameter will be active even if device is configured for
On/OFF control.
2) During the transfert from AUTO to MANUAL, if this action is
programmed as a not bumpless transfer, the “ñ.rñP” function
will be ignored and the output will step up to the value set by
“Añ.UL” [C.G04] parameter.
- Main output cycle time - [r.E07]
This parameter is available when time proportional main control
output is configured.
Range: from 1 to 200 s
- Servo motor dead band - [r.E03]
This parameter is available when the servomotor control drive
output is configured (“O3.Fn” [C.E03] is equal to “ñC.Sñ” or
“SC.Sñ” ).
Range: from 1% to 50%
- Main control output low limit - [r.E04]
This parameter is available when one control output is
configured as main output.
Range: from 0.0 % (of the output span) to ñ.OLH [r.E05]
- Main control output high limit - [r.E05]
This parameter is available when one control output is
configured as main output.
Range: from ñ.OLL [r.E04] to 100.0 % of the output span