4. INSTALLATION INSTRUCTIONS
CLEARANCE DISTANCES (COMBUSTIBLES & NON-COMBUSTIBLES)
The appliance comes with a rear heatshield, which must be installed, irrespective whether the
surrounding materials are combustible or non-combustible. Required distances to combustibles,
(with the supplied heatshield), can be found in the Product Specification section of this manual. If a
double wall flue pipe is used for the installation, the permitted distance to combustibles is reduced.
Recommended distances to non-combustibles are also indicated, in the same section.
FLUE DRAFT
An appropriate flue draft is essential, for the stove to work safely and efficiently. When installed,
and prior to commissioning, a flue draft reading should be taken, using the flue draft reading point
located in the top of the right hand side of the stove. When both the stove and chimney are warm,
a reading in a range between 1.25mm wg (12 Pa) and 2.5mm wg (25 Pa) should be expected. Any
readings significantly outside this range are likely to cause problems, so further investigation should
be undertaken so as to either reduce or increase the flue draft reading, as appropriate.
COMMISSIONING
Once the installation has been completed, check the flue and chimney connection is fully sealed, and
complete a test lighting of the stove. Instruct the owner on how to use the appliance, and complete
the Commissioning Checklist section of this manual. Finally, ensure that you leave this manual with
the owner, for their reference.