EasyManua.ls Logo

ETC B-Box4 - Connect ArcSystem Pro One-Cell Luminaires with an FD‑BBOX‑4 M

ETC B-Box4
11 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ETC Installation Guide
F-Drive B-Box4
F-Drive B-Box4 Page 5 of 11 ETC
Connect ArcSystem Pro One-CellLuminaires with an
FD-BBOX-4M
Connect up to four ArcSystem Pro standard, Small, or Micro luminaires to an F-Drive with a
FD-BBOX-4M. Visit the F-Drive System Design Tool at etcconnect.com/FDriveSysDesignTool to
learn more.
SENSE
1 2 3 4
DMX
IN
DMX
THRU
MAINTAIN
FDR12FD
FD-BBOX-4M
Ch 4
Ch 3
Ch 2
Ch 1
A
C
C
C
C
D
D
D
D
FDW1CCD (-CE)
A
B
B
Driver can be
W1 or R12
Description Notes
A
CC-150Card installed in
a card slot of an F-Drive
R12
The CC-150Card and W1CCDriver output constant current, adjustable from 200700mA. You
must configure each channel of the driver to provide the correct current for the connected
luminaire. See
Configure the Output Current on page11
.
W1CCDriver
B Category-type cable*
The cable from the RJ45 output of the driver to the input of the FD-BBOX-4M. You must use
0.25mm
2
(23AWG) or larger conductors in Category-type cable.
C
Use the cable attached
to the ArcSystem Pro
One-Cell luminaire
Extension cables are available. See the datasheets for ArcSystem Pro One-Cell luminaires at
etcconnect.com/Products/Architectural-Fixtures/Pro-One-Cell/Documentation.aspx.
D
ArcSystem Pro One-Cell
luminaire
ArcSystem Pro One-Cell (ARCP1), Pro One-Cell Small (ARCP1S), or Pro One-Cell Micro (ARCP1M);
White or Fade to Warm.
*See
Electrical and Wiring Specification on page8
.
Note:The illustration is not drawn to scale. Loads are not shown on all outputs of the F-Drive R12 for clarity.