EVCO S.p.A. c-pro 3 nano | Hardware Manual ver. 1.0 | Code 114CP3NE104
page 6 of 26
1.2 Main features of the models available and purchasing codes
The table below shows the main features of the models available and the purchasing codes.
MAIN FEATURES MODELS AVAILABLE AND PURCHASING CODES
c-pro 3 nano basic c-pro 3 nano CAN c-pro 3 nano plus
Power supply EPN2L EPN3L EPN2LXC EPN3LXC EPN2LXP EPN3LXP
12 VAC • • •
24 VAC/DC • • •
Analogue inputs EPN2L EPN3L EPN2LXC EPN3LXC EPN2LXP EPN3LXP
for PTC, NTC or Pt 1000 probes; can be configured
also for dry contact digital input
5 5 5 5 5 5
for NTC probes, 0-5 V ratiometric transducers, 0-10
V, 0-20 mA or 4-20 mA transducers; can be
configured also for dry contact digital input
2 2 2 2 4 4
Digital inputs EPN2L EPN3L EPN2LXC EPN3LXC EPN2LXP EPN3LXP
dry contact and for pulse trains up to 2 KHz 2 2 2 2 2 2
dry contact 1 1 1 1 3 3
Analogue outputs EPN2L EPN3L EPN2LXC EPN3LXC EPN2LXP EPN3LXP
for 0-10 V, PWM or phase cutting signal 2 2 2 2 2 2
for 0-10 V, 0-20 mA or 4-20 mA signal 2 2
Digital outputs EPN2L EPN3L EPN2LXC EPN3LXC EPN2LXP EPN3LXP
SPST electro-mechanical relay, 3 A res. @ 250 VAC 6 6 6 6 7 7
Communications ports EPN2L EPN3L EPN2LXC EPN3LXC EPN2LXP EPN3LXP
INTRABUS port (RS-485 MODBUS master/slave by
connecting the serial interface
EVIF22ISX)
1 1 1 1 1 1
RS-485 MODBUS port 1 1
CAN port 1 1 1 1
USB port 1 1 1 1 1 1
For more information see section TECHNICAL SPECIFICATIONS.