R02 Minimum time between 2 successive compressor starts 2 min 0 min 30 min 2 min
R03 Delay in activating the compressor after the activation of the card 15 sec 0 sec 300 sec 15 sec
R04 Minimum time between the switching on and off of the compressor 0 sec 0 sec 300 sec 0 sec
R07 Daily maximum limit of compressor use 90% 0% 100% 100%
R08 Maximum permissible SetPoint value 30°C 0°C 50°C 30C°
R09 Minimum permissible SetPoint value 5°C 0°C 50°C 0C°
R11 Delay Off On compressor 120 sec 0 300 sec 120 sec
R13 Hysteresis Hmidity 10%
R14 Duration steam injection 20 min
R15 Cycle length humidity 20 min
P. DESCRIPTION LISTA
FANS
F01 Enables evaporator fans (0 disabled; 1 Enabled) 1
F03 Evaporator fans set 50 C°
F05 Evaporator fans in defrost (0: OFF 1:ON) 0
F07 Delay activating evaporator fan from the end of defrost 240 sec
F13 Duration activation extractor fans 10 min
F14 Minimum speed fans 10%
F15 Maximum speed fans 90%
DEFROST SCHEDULE
H01 First defrost schedule (24 h = excluded) 24h
H02 First defrost schedule (24 h = excluded) 24h
H03 First defrost schedule (24 h = excluded) 24h
H04 First defrost schedule (24 h = excluded) 24h
PRINT
PR1 Sampling time 60 min 1 min 600 min 60 min
PR2 Type of daily printing (daily) 0 0 2 2
COMMUNICATION
ADD Instrument address1 1 147 1
SC Serial Management: 1
0 = not used
1 = print
2 = ModBus
MB1 BaudRate: 0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200 2
MB2 Parity : 0 = no parity; 1 = odd; 2 = even 2