Plus 12 Operator's Manual (164200090 Rev E)  48
. Connect the wires from the PDM to the UPS output terminal block as shown in
Figure 22. Refer to the label located on the inside of the PDM for terminal
block torque requirements. Use only #6ĆAWG 75°āC copper wire (minimum).
If you are using the optional hardwired PDM, connect the wiring to the terminal
block according to the label located on the inside of the PDM for the UPS output.
Use the conduit plate for conduit landing.
 The UPS contains its own energy source (battery). There is high
voltage present at terminals 8 and 9 (terminals for remote battery connection)
when a battery cabinet is connected to the UPS.
. Reattach the PDM terminal access plate.
. Turn the PDM circuit breaker(s) to the ON(l)position.
. Configure the UPS for bypass and input configuration (see page 45).
. Continue to UPS Startup and Shutdown" on page 21 to start up your UPS.