EasyManua.ls Logo

Extech Instruments 96VFL Series - Analog Output Wiring; Alarm Relay Output

Extech Instruments 96VFL Series
37 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VFL Series User Manual v2.0 10/20
9
4.8 Analog Output Wiring
Analog outputs are optional. Analog outputs are available across the same terminals that
are used for the relay outputs. See Control Relay terminals table above. Parameter Ct (PID
Menu 3) must be set to ‘0 when using an analog output.
4.9 Alarm Relay Output
One relay is supplied in a standard VFL controller, the second alarm is optional. Alarm relays
are normally open (N.O.) single-pole single-throw mechanical switches. The first alarm relay
is available on terminals 11 and 12. The optional secondary alarm relay is on terminals 12
and 13.
Alarm relays do not supply power and should be wired in series with power and the alarm
device.
Alarm relays are rated 3 Amps @ 110VAC or 24VDC (Resistive Loads).
In the diagram below terminals x and y represent the VFL rear terminal designations, see
the table below for the specific terminal numbers.
FIGURE 4.3 - NORMALLY OPEN (N.O.) ALARM WIRING
ALARM 1
ALARM 2
48VFL (x-y)
Terminals 5 and 6
Terminals 3 and 4
96VFL (x-y)
Terminals 13 and 14
Terminals 11 and 12

Table of Contents

Other manuals for Extech Instruments 96VFL Series

Related product manuals