2ND LEVEL PROGRAMMING
To access 2nd LEVEL PROGRAMMING, press push-
button F and, while holding it down, press push-
button “+.
If you release the push-button “+”, the display
shows the name of the first function.
If you also release the F push-button, the display
shows the value or parameter of that function,
which can be changed with the+ and keys.
If you press the F key again (and hold it down),
the display shows the name of the next function,
etc.
When you reach the last function, press the F
push-button to exit programming, and the
display resumes showing the input status.
The following table indicates the sequence of
functions accessible in 2nd LEVEL PROGRAMMING.
Page 29
January, 2007
620/640 Operator And
624BLD Control Panel Installation Manual
THE 624 BLD CONTROL PANEL INSTALLATION INSTRUCTIONS
2ND LEVEL PROGRAMMING
DISPLAY FUNCTION DEFAULT
MAXIMUM TORQUE AT THRUST:
The motor works at maximum
torque (ignoring the torque
adjustment) during the initial
time of the movement.
= Active
= Excluded
PRE-FLASHING:
To activate the flashing light for
5 sec before the start of the
movement
Excluded
Before every movement
Before closing
At end of pause only
SLOW CLOSING:
For setting the entire closing
stage at slow speed.
= Active
= Excluded
DECELERATION TIME AFTER
LIMIT-SWITCHES:
For setting deceleration time (in
seconds) after the opening and
closing limit-switches have been
activated. It can be adjusted from
0 to 10 sec, in one second steps.
= deceleration excluded
= maximum deceleration
WORK TIME (time out):
We advise you to set a value from
5 to 10 seconds longer than the
required by the automated
system to move from the closing
to the opening position and vice
versa. It can be adjusted from 0
to 59 sec in one second steps.
Next, the viewing changes in
minutes and tenths of a second
(separated by a dot) and time is
adjusted in 10 second steps, up
to the maximum value of 4.1
minutes.