18
ENGLISH
LOGIC "SA" PULSES
STATUS OF AUTOMATED SYSTEM
OPEN A OPEN B CLOSE STOP FSW OP FSW CL FSW CL/OP
CLOSED
opens and recloses after
the pause time
Opens the gate partially
and closes it after pause
time B
no effect
no effect
(OPEN inhibited)
no effect
(OPEN inhibited)
no effect
no effect
(OPEN inhibited)
DURING OPENING no effect (1) no effect recloses the gate locks operation see 2nd level prog. no effect
locks and opens on
disengagement
(stores CLOSE)
OPEN IN PAUSE recloses the gate (1) recloses the gate recloses the gate locks operation no effect
reloads pause time
(CLOSE inhibited)
reloads pause time
(CLOSE inhibited)
DURING CLOSING reopens the gate reopens the gate n o effect locks operation no effect
reverses to opening (see
2nd level prog.)
locks and opens on
disengagement
(stores CLOSE)
LOCKED closes the gate closes the gate closes the gate
no effect
(OPEN/CLOSE inhibited)
no effect
(OPEN inhibited)
no effect
(CLOSE inhibited)
no effect
(OPEN/CLOSE inhibited)
LOGIC bC
PULSES DURING OPENING/COMMANDS MAINTAINED
DURING CLOSING
PULSES
STATUS OF AUTOMATED SYSTEM
OPEN A / C LOS E STOP FSW OP FSW CL FSW CL/OP
CLOSED opens the gate / no effect
no effect
(OPEN inhibited)
no effect
(OPEN inhibited)
no effect
no effect
(OPEN inhibited)
DURING OPENING no effect / closes the gate locks operation see 2nd level prog. no effect
locks and opens on
disengagement (stores
OPEN/CLOSE)
OPEN no effect / closes the gate
no effect
(OPEN/CLOSE inhibited)
no effect
no effect
(CLOSE inhibited)
no effect
(OPEN/CLOSE inhibited)
DURING CLOSING opens the gate / no effect locks operation no effect
reverses to opening (see
2nd level prog.)
locks and opens on
disengagement (stores
OPEN/CLOSE)
LOCKED opens the gate / closes the gate
no effect
(OPEN/CLOSE inhibited)
no effect
(OPEN inhibited)
no effect
(CLOSE inhibited)
no effect
(OPEN/CLOSE inhibited)
LOGIC "B" PULSES
STATUS OF AUTOMATED SYSTEM
OPEN A / CLOSE STOP FSW OP FSW CL FSW CL/OP
CLOSED opens the gate / no effect
no effect
(OPEN inhibited)
no effect
(OPEN inhibited)
no effect
no effect
(OPEN inhibited)
DURING OPENING no effect / closes the gate locks operation see 2nd level prog. no effect
locks and opens on
disengagement (stores
OPEN/CLOSE)
OPEN no effect / closes the gate
no effect
(OPEN/CLOSE inhibited)
no effect
no effect
(CLOSE inhibited)
no effect
(OPEN/CLOSE inhibited)
DURING CLOSING opens the gate / no effect locks operation no effect
reverses to opening (see
2nd level prog.)
locks and opens on
disengagement (stores
OPEN/CLOSE)
LOCKED opens the gate / closes the gate
no effect
(OPEN/CLOSE inhibited)
no effect
(OPEN inhibited)
no effect
(CLOSE inhibited)
no effect
(OPEN/CLOSE inhibited)
LOGIC "C" COMMANDS MAINTAINED PULSES
STATUS OF AUTOMATED SYSTEM
OPEN A / C LOS E STOP FSW OP FSW CL FSW CL/OP
CLOSED opens the gate / no effect
no effect
(OPEN inhibited)
no effect
(OPEN inhibited)
no effect
no effect
(OPEN inhibited)
DURING OPENING no effect / closes the gate locks operation see 2nd level prog. no effect
locks and on disengage-
ment 2nd level prog.
OPEN no effect / closes the gate
no effect
(OPEN/CLOSE inhibited)
no effect
no effect
(CLOSE inhibited)
no effect
(OPEN/CLOSE inhibited)
DURING CLOSING opens the gate / no effect locks operation no effect locks operation locks operation
LOCKED opens the gate / closes the gate
no effect
(OPEN/CLOSE inhibited)
no effect
(OPEN inhibited)
no effect
(CLOSE inhibited)
no effect
(OPEN/CLOSE inhibited)
(2) When turned on, the board checks the inputs and if an OPEN A or B command is active, it opens the leaf or gate. Otherwise it closes it.
(1) During the partial opening cycle, an OPEN A pulse causes total opening