12
COOLING CYCLE PARAMETERS [CO1] - CHILLER
(example of parameterization with basic setting "mp420_50", see page 20)
Pressure of the voltage/speed V1 point.
Min. 0 bar Max. P2 Def. 20 bar
Pressure of the voltage/speed V2 point.
Min. P1 Max. P_MAX Def. 24 bar
Maximum production pressure, above this the output is at the voltage
MotorMaxLim.
Min. P2 Max. Full Scale Def. 25 bar
Voltage/speed of the pressure point P1.
Min. MotorMinLim Max. V2 Def. 20%
Voltage/speed of the pressure point P2.
Min. V1 Max. MotorMaxLim Def. 90%
CHILLER
CHILLER
CHILLER
20.0
P1
[IC]
bar
CHILLER
24.0
P2
[IC]
bar
CHILLER
20
V1
[IC]
%
CHILLER
25.0
P_MAX
[IC]
bar
CHILLER
90
V2
[IC]
%