Clearances in the electrical cabinet
Heat dissipation inside the cabinet
It is recommended to use the following to cool the
electrical cabinet:
Heat exchangers to avoid the entry of contaminated
air (vapor, suspended iron dust, etc.), eliminating the
possibility of accumulating particles, condensation,
etc. throughout the ventilation pathways.
air extractors ·fans· to prevent the entry of air into the
electrical cabinet.
Place the extractor fan at the top of the cabinet
and the air intake at the bottom.
To have a filter in the air input. It is also
recommended to install a filter in the fan.
Decrease the air intake speed from the outside by
making the air input window larger than that of the
fan. The required power and air flow depends on
the power installed.
Install the QC-PDS system as far away as
possible from air inputs and outputs.
Carry out periodic maintenance
on air filters.
Mechanical considerations
Electrical considerations
Electrical conditions
Power supply input.
3 AC, from 400 (1-10 %) V AC to 480 (1+10 %) V AC
DC BUS: 500/800 V DC
Electrical precautions
MANDATORY.
Inside the electrical cabinet, make sure to leave a
clearance of at least 10 cm (3.93 inches) between the
equipment and the top and bottom sections and the front
panel of the cabinet and any other obstacle obstructing
the flow, thereby providing better removal of heat.
MANDATORY.
The ventilation for the electrical cabinet must be enough
to dissipate the heat generated by all the devices and
components working inside.
Module
power dissipated at maximum load
QC-APS-15 63 W
QC-APS3-15 63 W
QC-PS-025 180 W
QC-PS-045 250 W
MAIN FILTER 42A-A 19 W
MAIN FILTER 75A-A 20 W
MAIN FILTER 275A 42 W
QC-BPM-100 5 W
QC-CM-75 0 W
Module
axis
4/8 kHz
spindle
S1
spindle
S6-40%
crest/mean
QC-RPS-030-FX
x
420 W 570/315 W
QC-RPS-160-XX
x
1860 W 2100/1200 W
QC-DR-007-FX 30/42 W x x
QC-DR-012-FX 53/68 W x x
QC-DR-021-FX 72/102 W
xx
QC-DR-030-FX 100/145 W 157 W 220/149 W
QC-DR-040-FX 142/201 W 213 W 301 W
QC-DR-055-FX 190/210 W 293 W 404/310 W
QC-DR-080-FX 255/370 W 405 W 560/305 W
QC-DR-120-FX 390/560 W 615 W 864/465 W
QC-DR-275-XX
x
1860 W 2100/1200 W
QC-DR-07+07-FD2 39/55 W
x
x
QC-DR-12+12-FD2 69/88 W x x
QC-DR-21+21-FD2 93/132 W x x
QC-DR-30+30-FD2 96/140 W x x
> 100 mm
AIR
AIR
AIR
AIR
> 100 mm
> 100 mm
3.93 in
3.93 in
3.93 in
> 100 mm
> 100 mm
3.93 in
3.93 in
> 100 mm
3.93 in
AIR
AIR
AIR
AIR
size | 0 | 1 | 3 size | 9
Terms Regulation Reference Test
Shipping
Vibration Meets:
IEC 60721-3-2
Class 2M1, sinusoidal
vibration
2 Hz
f
9 Hz, 3.5 mm
amplitude
9 Hz
f
200 Hz, 1 g
200 Hz
f
500 Hz, 1.5 g.
Jerk limit Meets:
IEC 60721-3-2
IEC 61800-2
Class 2M1,
packed unit
Operation
Ambient
sinusoidal
vibration tests
Meets:
CEI 60068-2-6,
Fc test
Sinusoidal vibration
10 Hz
f
57 Hz,
constant 0.075 mm
amplitude
57
Hz
f
150 Hz,
1 g constant acceleration
Degrees of
sealing pro-
tection
(code IP)
Meets:
EN 60529
Open IP xx.*
Always install inside
an electrical
cabinet.
* Open IP xx, to be installed inside a cabinet or assembly that provides the
required access protection.
Meets:
IEC 61800-5-1
Protection
Class
Class I
(with protective conductors)
Over-voltage, category III
Pollution Degree 2
Altitude
2 000 masl
Distribution diagrams: TN/TT
Diagrams with grounding on a vertex
are not permitted.
MANDATORY.
The electrical installation should be carried out in
compliance with standard IEC 60204-1.
MANDATORY.
The installation must be fully compliant with all the
requirements of the local and national electrical
regulations and all other applicable regulations.