QCQR-32/36
Q
uer
C
us - Power Drive System.
Q
uick
R
eference. Ref.2003
Power, feedback and grounding connections
A18. The lids of all the units must
be opened in order to connect the
+24 V DC through 2.5 mm² wires
FM7. SPINDLE MOTOR
FKM. FEED AXIS
SERVOMOTOR WITH BRAKE
FKM. FEED AXIS
SERVOMOTOR
MPC-4xS
to the X11A
to the X11B
MC-20/6
MPC-4xS+(2x1)
QC-EEC-X
EOC-12
EOC-12
MC-20/6
EOC-12
MC-20/6
15
1515
MPC-4xS
15
QC-EEC-FM7-X | QC-EEC-FM7C-X
PE WIRE TO THE GROUND SCREW
to the X11A
and X12 (B+/B-)
PE
PE WIRE TO THE
GROUND SCREW
X11A
PE
PE
E
U-V-W-PE
Z1-Z2-Z3-PE
(FAN)
MPC-4x1.5
L1-L2-L3-PE
3-ph 400/480 V AC
50/60 Hz
PE WIRE TO THE
GROUND SCREW
QC-DR-X-FS2
QC-DR-X-FS1
QC-DR-X+X-FD2
MPC-4xS
QC-EEC-X
QC-EEC-X
FKM. FEED AXIS
SERVOMOTOR
CNC QC
B10
SERCOS-III CONNECTION
1 A+/COS A+ signal / 1Vpp cosine signal generated by the encoder
2 A-/REFCOS A- signal / ref. level for the cosine signal 2.5 V DC
3 B+/SIN B+ signal / 1Vpp sine signal generated by the encoder
4 B-/REFSIN B- signal / ref. level for the sine signal 2.5 V DC
5 I0+/RS485+DATA+ I0+/I0- reference mark signals
6 I0-/RS485-DATA- Serial line signals, RS-485 type
DATA+/DATA-signals
·
EnDat/SSI/FeeDat
·
7 CLK+/REQ+ CLOCK+/CLOCK- signals
·
EnDat/SSI
·
8 CLK-/REQ- REQ+/REQ- signals
·
FeeDat
·
9 +5 V DC Supply voltage
10 +5 V DC Supply voltage
11 0 V DC Supply voltage reference
12 0 V D Supply voltage reference
13 TEMP- / N. C. Polarity (-) temperature thermistor / N. C.
14 +8 V DC Supply voltage
15 TEMP+ / N. C. Polarity (+) temperature thermistor / N. C.
MOTOR FEEDBACK IN:
QC-DR-X-FX
DIRECT FEEDBACK IN:
QC-DR-X-FS2
MOTOR FEEDBACK | B-AXIS IN:
QC-DR-X+X-FD2
MOTOR FEEDBACK | A-AXIS IN:
QC-DR-X+X-FD2
FEEDBACK PINOUT
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
15
PE
L1-L2-L3-PE
3-ph 400/480 V AC
50/60 Hz
A19 A20
L1'/T1 L2'/T2 L3'/T3
L1'-L2'-L3'-FE
L1' L2' L3'
L1 L2 L3
MPC-4xS
MAIN FILTER 42A-A
QC-PS-025
PE
> S/2
MAINS
LOAD
UPON REQUEST
QC-FBC-X 1 ... 7 m
QC-FBC-FLEX-X 10 ... 100 m
GREEN
ACCESSORY
QC-FBC-0.25
GREEN
ACCESSORY. SERCOS-III CABLE
QC-FBC-0.25
MPC-4xS
3+PE
3+2+PE
> S/2
time-lag
T 2.5 A
I²t < 200 A²s
3+PE
A19.
Take the
functional
ground
terminal FE to
the protection
ground PE
LINE VOLTAGE
LINE VOLTAGE
SHIELD
to GP-1
SHIELD to GP-1
SHIELD
GROUNDING PLATE
TOP
GP-1
shield
GP-2
PE WIRE TO THE GROUND SCREW
SHIELD to the GP-1
15
USE THE METAL PLIER TO PINCH THE
SHIELD OF THE POWER CABLE SO
IMPORTANT:
GROUNDING PLATE
BOTTOM
SHIELD
to GP-1
SHIELD
to the GP-2
MALLA
A GP-2
MALLA
A GP-2
MALLA
A GP-2
SHIELD
to the GP-2
SHIELD
metal clamp
QC-EEC-...
Take the ground
chassis to the
protection
ground PE
PE
MPC-...
GP-2
QC-PS-025
shield
metal clamp
GP-1
STRIP THE POWER CABLE
TO EXPOSE THE SHIELD
MPC-...
IT MAKES 360-DEGREE CONTACT WITH
THE GP-1 GROUND PLATE
IMPORTANT:
USE THE METAL PLIER TO PINCH THE
SHIELD OF THE FEEDBACK CABLE SO
STRIP THE FEEDBACK CABLE
TO EXPOSE THE SHIELD
IT MAKES 360-DEGREE CONTACT WITH
THE GP-2 GROUND PLATE