3.2 Non-regenerative power supplies
The non-regenerative QC-PS-
power supplies are part
of the FAGOR QuerCus-Power Drive System. They are
connected via the mains filter to the three-phase mains
with line voltages between 400 (1-10%) V AC and 480
(1+10%) V AC and line frequencies of between 50 (1-
4%) Hz and 60 (1+3.3%) Hz.
The QC-PS-025 power supply comes integrated with an
auxiliary power supply allowing for the system control
electronics to be supplied with +24 V DC.
The QC-PS-045 power supply does not come with any
auxiliary power supply and, therefore, it must ALWAYS
be installed with the QC-APS-15 external auxiliary power
supply to feed the system control electronics with +24 V
DC.
QC-PS-025 QC-PS-045
Status indicator LED's
D1|D2|D3 LEDs. Not being used.
D4|D5|D6 LEDs. Associated with the main power supply.
Connecto Function
A19
L1’/T1, L2’/T2, L3’/T3 terminals
Three-phase power input to the main power supply
A17
(+/-) DC BUS terminals under lid
A18
+24 V DC 7 A electric power supply output
X14
Basic control signals
X15
External braking resistor(s)
Leds D4 D5 D6 Function
red amber green
i
IOFFOFF
No errors. No line voltage or
PS ENABLE not enabled
ii
OFF OFF OFF
DC BUS loading in progress
iii
OFF OFF ON
DC BUS ready
iv
OFF ON ON
Crowbar circuit activation
iv
ON OFF ON
Error. Over-voltage at the DC BUS
v
ON OFF I
Error. I² t Crowbar
vi
ON ON OFF
Error. Short-circuit at the Crowbar IGBT
vii
ON ON ON
Error. Over-temperature at the heatsink
viii
ON ON I
Error. Soft-Start
I
: blinking
WARNING.
The DC BUS discharge period may extend for up to
10 min after the equipment has been disconnected from the elec-
trical mains. For this reason, always
ensure that there is no volt-
age in the DC BUS before handling the equipment.
X14
Characteristics
plate
Version/model
label
D1|D2|D3
not used
D4|D5|D6
RESET
button.
not used
A17
A18
Tightening
torque: 3 N·m
3x M5 screws
to connect
the PE
A19
X15
S16
.
External
braking resistor
selectors
Opening and
closing click cover
tool with bottom
pivot hinge
QC-PS-045
SIZE |1.
Width: 78 mm