Manual Bypass Function
A manual bypass button is located on the SSG front panel. When the UPS is operating from utility
power in online mode, depressing this button will cause the UPS to transfer to bypass. The bypass
condition transfers the connected equipment to the utility power source via an internal relay. During
bypass condition, the UPS inverter and battery backup operation is disabled. Depressing the bypass
button again will return the UPS to online mode.
Automatic Bypass Function
The SSG UPS will automatically switch to bypass to energize the connected load when the UPS is first
turned on, encounters an overload, over temperature condition, or failure condition. Should any of these
events occur, the UPS will transfer to bypass mode, sound an audible alarm and provide a bypass
indication on the LCD display. The output filter and the input filter stage maintain the conducted EMI
and RFI levels below FCC Class B limits.
Inspecting the Equipment
Visually inspect the UPS for shipping damage. If the equipment has been damaged during shipment,
and is signed for as received, make sure the receiver slip is noted with the detail of the damage
exception. Keep the shipping cartons and packing materials for the carrier, and immediately file a claim
for “shipping damage” with the carrier. If you discover damage after acceptance, file a claim for
“concealed damage.”
To file a claim for shipping damage or concealed damage:
You must file with the carrier within 24 hours of receipt of the equipment.
You must send a copy of the damage claim within 3 days to Falcon Electric, Inc.