INSTALLER VENTILATION COMBI POWER TUNNEL POWER tab page Cap.
Setting of the ventilation percentage at which fans should activate/deactivate and air
inlets open/close. The ventilation percentages must increase from the lowest to the
highest position.
The combi positions are also used for natural ventilation.
Setting of the required pressure for the corresponding position. A rule of thumb: the
higher the ventilation position, the lower the required pressure. Enter 0 to deactivate
pressure control.
Setting of the ventilation capacity (m3/hour) for all positions used. If ventilation is used
in m3/hour/animal, always fill in this column!
INSTALLER VENTILATION COMBI POWER TUNNEL TUNNEL tab page Exhaust
Setting of the temperature whereby the tunnel fan is active. Instead of the ventilation
position in % you enter the offset temperature for the positions. At the first position this
offset temperature is linked to start temperature ventilation + calculated bandwidth.
Each following position is linked to the previous position via an offset.