Installer
35
INSTALLER VENTILATION COMBI POWER TUNNEL POWER tab page Cap.
Position %
Setting of the ventilation percentage at which fans should activate/deactivate and air
inlets open/close. The ventilation percentages must increase from the lowest to the
highest position.
The combi positions are also used for natural ventilation.
Pressure Pa
Setting of the required pressure for the corresponding position. A rule of thumb: the
higher the ventilation position, the lower the required pressure. Enter 0 to deactivate
pressure control.
Cap. m3/h
Setting of the ventilation capacity (m3/hour) for all positions used. If ventilation is used
in m3/hour/animal, always fill in this column!
INSTALLER VENTILATION COMBI POWER TUNNEL TUNNEL tab page Exhaust
Position °
Setting of the temperature whereby the tunnel fan is active. Instead of the ventilation
position in % you enter the offset temperature for the positions. At the first position this
offset temperature is linked to start temperature ventilation + calculated bandwidth.
Each following position is linked to the previous position via an offset.