EasyManuals Logo

Fancom LUMINA 16 User Manual

Fancom LUMINA 16
67 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #38 background imageLoading...
Page #38 background image
Installer
34
Con. / Mod. %
The entry depends on the system setting Power-part in HOUSE SETUP, tab page
Combi.
Con.: Enter the positions of the linear controllable fans.
Mod. %: The control computer uses the set ventilation percentage to calculate the
on and off times for the modulating fans. (This column is only present if modulating
fans are used).
Con. Extra
Enter the positions of the extra linear controllable fans (only if extra controllable fans are
used).
Relays
0 = fan off
1 = fan on
M = modulating fan (This option is only possible if modulating fans are used)
INSTALLER VENTILATION COMBI POWER TUNNEL POWER tab page Inlet
Position %
Setting of the ventilation percentage at which fans should activate/deactivate and air
inlets open/close. The ventilation percentages must increase from the lowest to the
highest position.
The combi positions are also used for natural ventilation.
Inlet %
Setting of the required inlet positions.
Natural %
Setting of the required positions of natural ventilation (this position is not used in the
natural ventilation phase, only during the Power phase).
Tunnel %
Setting of the required inlet positions (if the tunnel inlet is not used, you may enter the
summer inlet position at tunnel inlet position).
Pressure Pa
Setting of the required pressure for the corresponding position. A rule of thumb: the
higher the ventilation position, the lower the required pressure. Enter 0 to deactivate
pressure control.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fancom LUMINA 16 and is the answer not in the manual?

Fancom LUMINA 16 Specifications

General IconGeneral
BrandFancom
ModelLUMINA 16
CategoryDesktop
LanguageEnglish