EasyManua.ls Logo

FANUC R-J3iB - 6.1 READING AND WRITING I;O SIGNALS (%I, %Q, %M, %AI, %AQ)

Default Icon
90 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.ADDRESS ASSIGNMENT TO POINTS OPERATION B-82604EN/01
- 22 -
6.1 READING AND WRITING I/O SIGNALS
(%I, %Q, %M, %AI, %AQ)
CIMPLICITY can read and write DI[1] of robot controller as PLC
address %Q1. Robot controller I/O signals correspond to PLC
addresses on a one-to-one basis as listed below.
Robot controller I/O signal PLC address Example
Digital Input DI[x]
%Qx DI[1] %Q1
Digital Output DO[x]
%Ix DO[1] %I1
Robot Input RI[x]
%Q(5000+x) RI[1] %Q5001
Robot Output RO[x]
%I(5000+x) RO[1] %I5001
UOP Input UI[x]
%Q(6000+x) UI[1] %Q6001
UOP Output UO[x]
%I(6000+x) UO[1] %I6001
SOP Input SI[x]
%Q(7000+x) SI[0] %Q7001
SOP Output SO[x]
%I(7000+x) SO[0] %I7001
Weld Input WI[x]
%Q(8000+x) WI[0] %Q8001
Weld Output WO[x]
%I(8000+x) WO[0] %Q8001
Wire Stick Input WSI[x]
%Q(8400+x) WSI[0] %Q8400
Wire Stick Output WSO[x]
%I(8400+x) WSO[0] %Q8401
Group Input GI[x]
%Aqx GI[1] %AQ1
Group Output GO[x]
%Aix GO[1] %AI1
Analog Input AI[x]
%AQ(1000+x) AI[1] %AQ1001
Analog Output AO[x]
%AI(1000+x) AO[1] %AI1001
PMC keep relay
DO[x] (x : 10001 – 10144)
Ka.b
%Ix
%I((a*8)+b+10001)
DO[10001] %I10001
K2.5 %I10022
PMC internal relay
DO[x] (x : 11001 – 23000)
Ra.b
%M(x-11000)
%M((a*8)+b+1)
DO[11001] %M1
R2.5 %M22
PMCdata table
GO[x] (x : 10001 – 12000)
D(a*2), D((a*2)+1)
%AI(x-6000)
%AI(a+4001)
GO[10001] %AI4001
D4, D5 %AI4003
CAUTION
In the PLC address, %I and %AI are input signals,
and %Q and %AQ are output signals. When robot
controller data is read and written, however, the
robot controller input signals correspond to %Q
and %AQ, and the robot controller output signals
correspond to %I and %AI. Note that, therefore,
the meanings of the robot controller signals are
opposite to those of the PLC signals.

Related product manuals