III- 19
COMPATIBLE 4-WIRE SMOKE DETECTORS
FOR 15220A AND 15240A FIRE ALARM CONTROL PANELS
Compatible 4-Wire Smoke Detectors must have a minimum absolute voltage range of 19 to 28 V.D.C.
DECTECTOR MANUFACTURER MAXIMUM MAXIMUM
W/BASE DETECTOR STANDBY ALARM
ORDER NO. W/BASE CURRENT CURRENT NOTES
AIR PRODUCTS & CONTROLS
9269 RW-DC-N 0.081ma. 115ma. MUST USE EOL RELAY
9270 RW-DC-P 0.110ma. 115ma. MUST USE EOL RELAY
APOLLO FIRE DETECTORS LIMITED
9260 w/9266 55000-350 w/46281-227 0.130ma. 100ma. MUST USE EOL RELAY
9261 w/9266 55000-250 w/46281-227 0.081ma. 100ma. MUST USE EOL RELAY
9264 w/9266 55000-153 w/46281-227 0.086ma. 100ma. MUST USE EOL RELAY
9274 w/9266 55000-152 w/46281-227 0.096ma. 100ma. MUST USE EOL RELAY
9259 w/9266 55000-150 w/46281-227 0.086ma. 100ma. MUST USE EOL RELAY
9221 w/9266 55000-151 w/46281-227 0.086ma. 100ma. MUST USE EOL RELAY
9222 w/9266 55000-380 w/46281-227 0.205ma. 100ma. MUST USE EOL RELAY
DETECTION SYSTEMS, INC. (DSI)
9195 W/9198 DS200 W/MB200-4W 0.025ma. 36ma. MUST USE EOL RELAY
9196 W/9198 DS200HD W/MB200-4W 0.025ma. 36ma. MUST USE EOL RELAY
KIDDE-FENWAL INC.
9472 W/9488 PSD7125 W/ 0.100ma. 20ma. MUST USE EOL RELAY
70-201000-101 35ma. w/Remote LED
9473 W/9488 PSD7126 W/ 0.100ma. 20ma. MUST USE EOL RELAY
70-201000-101 35ma. w/Remote LED
9474 W/9489 PSD7129 W/ 40ma. 100ma. MUST USE EOL RELAY
DH-22 OR 6 WIRES
9475 W/9488 PSD7130 W/ 0.100ma. 20ma. MUST USE EOL RELAY
70-201000-101 35ma. w/Remote LED
9476 W/9488 PSD7131 W/ 0.100ma. 20ma. MUST USE EOL RELAY
70-201000-101 35ma. w/Remote LED
9495 W/9488 CPD7021 W/ 0.060ma. 20ma. MUST USE EOL RELAY
70-201000-101 35ma. w/Remote LED
9495 W/9489 CPD7021 W/ 40ma. 100ma. MUST USE EOL RELAY
DH-22 OR 6 WIRES
HOCHIKI-AMERICA CORP. ALPHA-LARM DIV.
9225 W/9230 SLK-24F W/HS-2RB/4 0.200ma. 26ma. MUST USE EOL RELAY
9226 W/9230 SLK-24FH W/HS-2RB/4 0.200ma. 26ma. MUST USE EOL RELAY
9227 W/9230 SIF-24F W/HS-2RB/4 0.200ma. 26ma. MUST USE EOL RELAY
9228 W/9230 SIH-24F W/HS-2RB/4 0.200ma. 26ma. MUST USE EOL RELAY
9234 AL-HADH-UP4 0.200ma. 26ma. MUST USE EOL RELAY
9233 AL-SPA-24B 0.25ma. 40ma. MUST USE EOL RELAY
AND 6 WIRES
firealarmresources.com