TECHNICAL DATA AND PERFORMANCE - BASE VERSION (VB)
Frame
1 2
Model
19.1 22.1 26.1 30.1 35.1 40.1
U.M.
NET NOMINAL performances - Base setting up (AB) - Standard plants - EUROVENT certified data
Frame
1 2
Model
19.1 22.1 26.1 30.1 35.1 40.1
U.M.
NET NOMINAL performances - Base setting up (AB) - Radiant plants
IR
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 20,1 22,3 26,1 31,5 36,6 41,3
kW
Power input 6,51 7,15 8,29 10,3 11,9 13,5
kW
EER 3,09 3,12 3,15 3,06 3,08 3,06
W/W
ESEER
3,44 3,48 3,51 3,44 3,45 3,45 W/W
Water flow rate plant side 3466 3844 4496 5439 6315 7138
l/h
Pressure drops plant side 26 32 26 37 32 41
kPa
IP
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 19,7 21,9 25,6 30,9 35,9 40,5
kW
Power input 6,45 7,08 8,20 10,2 11,8 13,4
kW
EER 3,05 3,09 3,12 3,03 3,04 3,02
W/W
ESEER 3,40 3,46 3,47 3,42 3,40 3,40
W/W
Water flow rate plant side 3398 3775 4410 5337 6194 7001
l/h
Pressure drops plant side 25 31 25 36 31 39
kPa
Heating A7W45 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 21,2 23,5 27,4 33,3 38,6 43,8
kW
Power input 6,21 6,82 7,89 9,79 11,3 12,9
kW
COP 3,41 3,45 3,47 3,40 3,42 3,40
W/W
Water flow rate plant side 3603 3995 4661 5651 6556 7427
l/h
Pressure drops plant side 28 34 28 40 34 43
kPa
Frame
1 2
Model
19.1 22.1 26.1 30.1 35.1 40.1
U.M.
NET NOMINAL performances - Base setting up (AB) - Standard plants
Data declared according to EN 14511. The values are referred to units without options and accessories.
IP
Heating A2W45 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 17,5 19,5 22,7 27,5 31,9 36,2
kW
Power input 6,12 6,70 7,78 9,62 11,1 12,7
kW
COP 2,86 2,91 2,92 2,86 2,87 2,85
W/W
Water flow rate plant side 2971 3312 3859 4678 5430 6147
l/h
Pressure drops plant side 19 24 19 28 24 30
kPa
IR
Cooling A35W18 ( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity 26,1 28,9 33,9 40,8 47,4 53,5
kW
Power input 6,67 7,35 8,49 10,60 12,2 13,9
kW
EER 3,91 3,93 3,99 3,85 3,89 3,85
-
Water flow rate plant side 4517 4998 5856 7076 8209 9291
l/h
Pressure drops plant side 43 52 43 62 53 67
kPa
IP
Cooling A35W18 ( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity 25,5 28,4 33,2 40,0 46,5 52,5
kW
Power input 6,60 7,27 8,40 10,5 12,1 13,7
kW
EER 3,86 3,91 3,95 3,81 3,84 3,83
-
Water flow rate plant side 4414 4912 5736 6938 8055 9102
l/h
Pressure drops plant side 41 50 41 59 51 64
kPa
Heating A7W35 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 21,6 24,0 28,0 34,0 39,4 44,7
kW
Power input 5,24 5,76 6,66 8,28 9,57 10,9
kW
COP 4,12 4,17 4,20 4,11 4,12 4,10
-
Water flow rate plant side 3686 4097 4783 5794 6720 7611
l/h
Pressure drops plant side 29 36 29 42 36 46
kPa
Heating A2W35 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 17,9 19,9 23,3 28,2 32,6 37,1
kW
Power input 5,15 5,64 6,54 8,10 9,39 10,7
kW
COP 3,48 3,53 3,56 3,48 3,47 3,47
-
Water flow rate plant side 3051 3394 3977 4817 5571 6326
l/h
Pressure drops plant side 20 25 21 30 25 32
kPa
Data declared according to EN 14511. The values are referred to units without options and accessories.