TECHNICAL DATA AND PERFORMANCE - BASE VERSION (VB)
Frame
1 2
Model
19.1 22.1 26.1 30.1 35.1 40.1
U.M.
NET NOMINAL performances - Low noise setting up (AS) - Standard plants - EUROVENT certified data
Frame
1 2
Model
19.1 22.1 26.1 30.1 35.1 40.1
U.M.
NET NOMINAL performances - Low noise setting up (AS) - Radiant plants
IR
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 19,3 21,4 25,1 30,3 35,2 39,8
kW
Power input 7,02 7,71 8,94 11,1 12,8 14,4
kW
EER 2,75 2,78 2,81 2,73 2,75 2,76
W/W
ESEER 3,06 3,10 3,12 3,07 3,08 3,09
W/W
Water flow rate plant side 3329 3689 4324 5234 6074 6864
l/h
Pressure drops plant side 24 29 24 35 30 38
kPa
IP
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 18,9 21,0 24,6 29,7 34,5 39,0
kW
Power input 6,95 7,63 8,84 11,0 12,7 14,3
kW
EER 2,72 2,75 2,78 2,70 2,72 2,73
W/W
ESEER 3,03 3,07 3,09 3,04 3,05 3,05
W/W
Water flow rate plant side 3260 3621 4238 5131 5954 6726
l/h
Pressure drops plant side 23 28 23 34 29 36
kPa
Heating A7W45 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 20,1 22,3 26,1 31,7 36,7 41,7
kW
Power input 5,95 6,54 7,56 9,38 10,9 12,4
kW
COP 3,38 3,41 3,45 3,38 3,37 3,36
W/W
Water flow rate plant side 3415 3790 4439 5378 6232 7069
l/h
Pressure drops plant side 25 31 25 36 31 40
kPa
Frame
1 2
Model
19.1 22.1 26.1 30.1 35.1 40.1
U.M.
NET NOMINAL performances - Low noise setting up (AS) - Standard plants
Data declared according to EN 14511. The values are referred to units without options and accessories.
IP
Heating A2W45 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 16,5 18,5 21,6 26,1 30,2 34,3
kW
Power input 5,87 6,43 7,46 9,22 10,7 12,1
kW
COP 2,81 2,88 2,90 2,83 2,82 2,83
W/W
Water flow rate plant side 2817 3142 3671 4439 5139 5839
l/h
Pressure drops plant side 17 22 18 25 22 28
kPa
IR
Cooling A35W18 ( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity 25,0 27,8 32,6 39,3 45,6 51,5
kW
Power input 7,18 7,91 9,14 11,4 13,1 14,8
kW
EER 3,48 3,51 3,57 3,45 3,48 3,48
-
Water flow rate plant side 4328 4809 5633 6818 7900 8930
l/h
Pressure drops plant side 40 48 40 57 49 62
kPa
IP
Cooling A35W18 ( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity 24,5 27,2 31,9 38,6 44,8 50,5
kW
Power input 7,10 7,81 9,04 11,2 12,9 14,7
kW
EER 3,45 3,48 3,53 3,45 3,47 3,44
-
Water flow rate plant side 4242 4706 5513 6681 7745 8759
l/h
Pressure drops plant side 38 47 38 55 47 60
kPa
Heating A7W35 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 20,5 22,8 26,6 32,3 37,4 42,5
kW
Power input 5,02 5,52 6,38 7,92 9,17 10,5
kW
COP 4,08 4,13 4,17 4,08 4,08 4,05
-
Water flow rate plant side 3497 3891 4543 5503 6377 7234
l/h
Pressure drops plant side 26 32 27 38 33 42
kPa
Heating A2W35 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 16,9 18,9 22,1 26,7 31,0 35,2
kW
Power input 4,93 5,42 6,28 7,76 9,00 10,3
kW
COP 3,43 3,49 3,52 3,44 3,44 3,42
-
Water flow rate plant side 2897 3223 3771 4560 5297 6000
l/h
Pressure drops plant side 19 23 19 27 23 29
kPa
Data declared according to EN 14511. The values are referred to units without options and accessories.