Exclusion
Quickly, triple click the S1 switch.
Product Usage
Range test
To make Z-Wave range test possible, the device must be added to the Z-Wave controller. Testing
may stress the network, so it is recommended to perform the test only in special cases.
The device has a built in Z-Wave network main controller’ s range tester.
Follow the below instructions to test the main controller’ s range:
1. Switch off the mains voltage (disable the fuse).
2. Remove the device from the wall switch box.
3. Switch on the mains voltage.
4. Press and hold the B-button to enter the menu.
5. Wait for the visual LED indicator to glow violet.
6. Quickly release and click the B-button again.
7. Visual indicator will indicate the Z-Wave network’ s range (range signalling modes
described below).
8. To exit Z-Wave range test, click the B-button.
Note: Communication mode of the device may switch between direct and one using routing,
especially if the device is on the limit of the direct range.
Z-Wave range tester signaling modes:
Visual indicator pulsing green – the device attempts to establish a direct communication with
the main controller. If a direct communication attempt fails, the device will try to establish a
routed communication, through other modules, which will be signalled by visual indicator
pulsing yellow.
Visual indicator glowing green – the device communicates with the main controller directly.
Visual indicator pulsing yellow – the device tries to establish a routed communication with the
main controller through other modules (repeaters).
Visual indicator glowing yellow – the device communicates with the main controller through the
other modules. After 2 seconds the device will retry to establish a direct communication with the
main controller, which will be signalled with visual indicator pulsing green.