Tips for Better Evacauations
Remove schrader cores and depressors with a core removal tool.
Use shortest vacuum rated hoses with largest diameter available.
Do not evacuate through hoses with low loss ttings.
Inspect the rubber seals at both ends of your hoses for damage.
Change pump oil before and during the job. Change pump oil on-
the-y without losing vacuum with Fieldpiece vacuum pumps.
When the vacuum pump is blocked, a slow rise that stabilizes may
signify moisture is still present in the system. A continuous rise to
atmosphere indicates a leak. Check hoses, tools, or the system itself.
Measurements are less representative of the entire system when
the vacuum pump is on because pumping creates a pressure
gradient. Block the pump and allow the system to stabilize before
assuming the measurement is of the entire system.