EasyManua.ls Logo

Fincor 2600 Series - User Manual

Default Icon
51 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
BOOK0795-F
Rev. 11/01
SERIES 2600/2610
SINGLE-PHASE
ADJUSTABLE-SPEED
DC MOTOR CONTROLLERS
(1/6 - 5 HP)

Table of Contents

Questions and Answers

  • J
    Jimmy BaileyAug 20, 2025
    What to do if the Fincor Controller fuse blows when AC line power is applied?
    • A
      Adam OlsenAug 20, 2025
      If the controller fuse blows when AC line power is applied, it could be due to several issues: * Faulty or incorrect wiring. Check all external wiring terminating in the controller and correct accordingly. * A grounded circuit, component, or wiring. Remove the ground fault. * Shorted SCRs or Varistor RV1, or Shunt Field Bridge BR1. Replace the shorted components or the control board. * A shorted or grounded motor shunt field. Repair or replace the motor. * Control board failure. Replace the control board.
  • M
    Monica DuarteAug 22, 2025
    Why does the Fincor 2600 fuse blow while the motor is running?
    • W
      William LeeAug 23, 2025
      The controller fuse blowing while the motor is running can be caused by: * An overloaded motor. Check shunt field current; low shunt field current causes excessive armature current. If field current is adequate, check for a mechanical overload. Also, check for a shorted motor armature or incorrect gear ratio, and correct accordingly. * A loose, corroded, faulty, incorrect, or grounded connection or wiring. Inspect all terminals, connections, and wiring between the line, controller, and motor. * A shorted or grounded motor. Repair or replace the motor. * Failing SCRs or Diode D1. Replace shorted devices or the control board. * Control board failure causing SCR false firing or misfiring. Replace the control board.
  • M
    Michael GomezAug 26, 2025
    How to increase the top speed of my Fincor 2600 Controller motor?
    • L
      lesliewrightAug 26, 2025
      If the motor won’t reach top speed, consider the following: * Check for rated line voltage, ±10%, on the controller line terminals, as low line voltage can be a cause. * The motor may be overloaded. Check the shunt field current. Low shunt field current causes excessive armature current. If the field current is adequate, check for a mechanical overload. Also check for a shorted motor armature or incorrect gear ratio and correct accordingly. * The maximum speed or current limit may be set too low. Turn the MAX SPD and CUR LMT potentiometers clockwise. * The motor field may be demagnetized. Replace the motor. * Control board failure. Replace the control board.
  • K
    Kimberly DennisAug 27, 2025
    What causes the Fincor 2600 Controller fuse to blow when starting?
    • C
      Christine JordanAug 28, 2025
      If the controller fuse blows when a Start command is initiated, it could be due to: * Shorted SCRs or Diode D1. Replace shorted devices or the control board. * A shorted or grounded motor. Repair or replace the motor. * Control board failure causing SCR’s to turn-on fully. Replace the control board.
  • E
    Elizabeth JohnsonAug 30, 2025
    How to fix unstable speed on a Fincor 2600?
    • N
      nancy30Aug 30, 2025
      If you are experiencing unstable speed, consider the following: * Fluctuating AC line voltage. Observe line voltage with a voltmeter or oscilloscope and correct the condition accordingly. * Loose or corroded connections or faulty wiring. Check all terminals, connections, and wiring between the line, operator controls, controller, and motor. * An oscillating load connected to the motor. Stabilize the load; turning the IR/TACH potentiometer counterclockwise may minimize oscillations. * A faulty motor. Check motor brushes, replace if needed, or repair/replace the motor. * A faulty tachometer generator or coupling (if used). Repair accordingly.
  • J
    Jennifer GoodwinSep 1, 2025
    How to reduce excessive maximum speed on a Fincor Controller?
    • E
      Eugene WilliamsSep 2, 2025
      To reduce excessive maximum speed: * Turn the MAX SPD potentiometer counter-clockwise, as the maximum speed may be set too high. * Check the motor shunt field and associated circuitry for a loose connection or a broken wire. Repair accordingly. * The motor field may be demagnetized. Replace the motor.
  • D
    Donald WilliamsSep 4, 2025
    How to decrease the minimum speed of a Fincor 2600 Controller?
    • K
      Krista EricksonSep 4, 2025
      If the minimum speed is excessive, turn the MIN SPD potentiometer counter-clockwise. Alternatively, the control board may have failed, and you should replace it.
  • B
    brownjosephSep 7, 2025
    What causes excessive line and motor armature current in a Fincor 2600?
    • R
      Richard WhiteheadSep 7, 2025
      Excessive line and motor armature current can be caused by an overloaded motor. Check the shunt field current, as low shunt field current causes excessive armature current. If the field current is adequate, check for a mechanical overload. Also check for a shorted motor armature or incorrect gear ratio, and correct accordingly.
  • J
    Jacob YatesSep 9, 2025
    What should I do if the Fincor 2600 Controller motor thermal guard tripped?
    • C
      Cassandra StoutSep 9, 2025
      If the motor thermal guard tripped, consider the following: * Ensure sufficient ventilation by removing dirt, dust, and debris from the motor intake and exhaust screens. * Reduce the load or increase the speed if there is excessive motor load at low speed. * Check for misalignment and realign the motor, as the motor may be overheating from friction. * Repair or replace the motor if there are shorted motor windings or faulty bearings.
  • D
    deborah71Sep 12, 2025
    What causes the shunt field current to be too high in my Fincor 2600 Controller?
    • B
      Bryce PerezSep 12, 2025
      If the shunt field current is too high: * Check the motor rating, as the shunt field may be connected for incorrect voltage. * Measure the shunt field resistance and compare with the motor rating, as the shunt field windings may be shorted. Repair or replace the motor if needed.

Summary

SAFETY WARNINGS

OPERATOR & PERSONNEL SAFETY

Responsibilities, qualified personnel, safety glasses, power disconnection warnings.

ELECTRICAL HAZARDS & COMPLIANCE

AC voltage hazards, code compliance for disconnects, and grounding requirements.

ENVIRONMENTAL & HANDLING SAFETY

Atmosphere precautions, static electricity risks, and safe board handling.

GENERAL INFORMATION

INSTALLATION

CONTROLLER MOUNTING

Specifies how and where to mount controllers for optimal operation and safety.

BRANCH CIRCUIT PROTECTION

Requirements for AC line fuses or circuit breakers for controller protection.

LINE SUPPLY

Guidelines for connecting the controller to the AC power supply, including voltage and KVA.

GROUNDING

Essential procedures for properly grounding the controller, motor, and operator stations.

INSTALLING THE CONTROLLER

Step-by-step instructions for the physical installation and initial checks of the controller.

INITIAL STARTUP

Procedures for powering up and performing initial checks and calibration after installation.

OPERATION

RUN

How to start and run the motor, controlling speed via potentiometers or signals.

STOP

Procedures for stopping the motor, including dynamic braking capabilities.

SPEED CONTROL

How to adjust motor speed using onboard or external controls.

INOPERATIVE MOTOR

Troubleshooting steps for a motor that stops or fails to start, including fuse checks.

MAINTENANCE AND REPAIR

ACCELERATION

Adjusting the rate at which the motor reaches its set speed.

TROUBLESHOOTING

Comprehensive guide to diagnosing and resolving common controller and motor issues.

RATINGS AND SPECIFICATIONS

Fincor 2600 Series Specifications

General IconGeneral
BrandFincor
Model2600 Series
CategoryController
LanguageEnglish

Related product manuals