Remote Supply With Resettable and Nonresettable Power Applications
FCPS-24FS PN 51883:B 12/04/02 33
Notes: The following notes apply to Figure 5.4 on page 32.
1. An End-of-Line Resistor must be installed between TB5, Terminal 1 (trouble
relay common) and the monitor module input circuit for module wiring
supervision (the ELR value is dependent on the module employed).
2. An End-of-Line power supervision relay must be connected between TB4,
Terminals 5 & 6. The Normally Closed (when energized) power supervision
relay contact must be in series with the End-of-Line Resistor referred to in note 1.
3. Do not loop wires under screw terminals. Break wires to maintain proper
supervision.
4. For a list of compatible devices, refer to the Device Compatibility Document.