EasyManua.ls Logo

Fire-Lite LCD-80F - Section 2: Operation; 2.1 Display Patterns

Fire-Lite LCD-80F
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation Display Patterns
15
Document 51338 Rev. B 08/24/05 P/N 51338:B
Section 2: Operation
2.1 Display Patterns
The LCD-80F Annunciator directly displays (mimics) the information
on the FACP display with the following exceptions:
Upon Power-up, the LCD-80F may display the following
message until a valid message is received from the FACP
If an LCD-80F Annunciator fails to receive communications
from the panel for a period of over 30 seconds, it will activate its
local sounder (if so programmed) and display the following
message:
A Communication Fault may be due to one of the following
conditions:
FACP has not been programmed to communicate with the
LCD-80F. Refer to the appropriate FACP manual
programming section.
EIA-485 wiring between the LCD-80F and FACP has an
open.
Polarity of the EIA-485 wiring between the LCD-80F and
FACP has been reversed. EIA-485 (-) on the LCD-80F
must be connected to EIA-485 (-) on the FACP and
EIA-485 (+) on the LCD-80F must be connected to
EIA-485 (+) on the FACP.
INITIALIZING...
PLEASE WAIT
COMMUNICATION FAULT!

Related product manuals