Commercial Fire Installation Guidelines
• Dress field wiring away from the microprocessor (center) section of the PC board. Dress wiring to the left and right
sides of the cabinet and secure using tie wraps.
• Separate all power-limited wiring from other wiring by at least ¼-inch (6.4mm).
• Non-power-limited wiring that exits the control panel (i.e., facility power) must be run in conduit.
• All unused knockouts must be plugged.
• All wiring that exits the control panel must be strain-relieved (e.g., tie-wrapped).