Section 2 – Installing the Control
2-3
5110XM-004-V1
+
Battery
+
Battery
Wires must be
run in Conduit
Cabinet
Door
Wired to
Transformer
Facility
Ground
Standoff
Standoffs
(3)
J5
Back
Plate
Standoff
LED Indicator
Board
Figure 2-3: Circuit Board Installation
Commercial Fire Installation Guidelines
Dress field wiring away from the microprocessor (center) section of the PC board. Dress wiring to the left and right
sides of the cabinet and secure using tie wraps.
Separate all power-limited wiring from other wiring by at least ¼-inch (6.4mm).
Non-power-limited wiring that exits the control panel (i.e., facility power) must be run in conduit.
All unused knockouts must be plugged.
All wiring that exits the control panel must be strain-relieved (e.g., tie-wrapped).