UL864 Compliance Requirements
•••••••••••••••••••••••••••••••••••••••••••••••••
General Information
The FA2000C provides features that allow the system to comply with UL864 installation
requirements. The following features must be set accordingly in order for the system to comply with
UL864 installation requirements:
The reporting of bypassed points to the central station must be enabled
Fire alarm notification circuits must be supervised
Fire installations require the use of a synchronization module to synchronize the sounders
and strobes on the system
Supervision must be enabled for both the main and backup phone lines
The delay water flow points must not exceed 90 seconds
The Test report interval must be set for a maximum of 24 hours
Non-Compliant UL864 Features
The following features are not UL864 compliant and may not be used in a UL864 installation:
Ring Detection Count must be set to 0 (disabled)
Programming Field Settings for UL864 Compliance
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements
in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features
or options must be limited to specific values or not used at all as indicated below.
Program feature or option
Permitted in
UL864? Y/N
Possible settings Settings permitted in UL 864
30 ALARM BELL
TIMEOUT
Y
0 = no timeout
1 = 4 minutes
2 = 8 minutes
3 = 12 minutes
4 = 16 minutes.
Must be a minimum of 6
minutes.
31 AUXILIARY RELAY
TIMEOUT
Y
0 = no timeout
1 = 4 minutes
2 = 8 minutes
3 = 12 minutes
4 = 16 minutes.
Must be a minimum of 6
minutes.
95 RING DETECTION
COUNT
Y
Enter 0 to disable ring
detection.
Enter 1-9, #10, #11, #12, #13,
#14 for ring counts of 1-14.
Enter #15 to select Answering
Machine Defeat Mode
Must be set to “0” (disable).