FA2000C Installation and Setup Guide 
4-4 
FIELD
 
TITLE and DATA ENTRIES  EXPLANATION 
 
0
600 
Trouble Report Code 
 
Enter the report code for a trouble condition. 
 
0
610 
Bypass Report Code 
 
Enter the report code when a zone is manually bypassed. 
 
0
620 
AC Loss Report Code 
 
Enter the report code for an ac loss condition.  This report is sent at a random 
time between 6 and 12 hours after ac power is lost.  If the ac restores before 
the report is sent, no ac loss report is sent. 
 
0
630 
Low Battery Report Code 
 
Enter the report code for a system low battery condition. 
 
0
640 
Normal Test Report Code 
 
Enter the report code for a normal test report. 
 
0
690 
Group Restores for Trouble, 
Bypass 
0 = disable 
1 = enable 
If enabled, the system sends the restore report only after all zones are 
restored.  If disabled, the system sends the report after each individual zone 
restores. 
 
0
700 
Alarm Restore Report Code (1st 
digit) 
 
Enter the first digit of the alarm restore report code.  The second digit is 
automatically sent as the 2nd digit of the zone alarm report code programmed 
in field 
56 for that zone, if expanded or 4+2 format is selected. 
 
0
710 
Trouble Restore Report Code 
 
Enter the restore report code for a restoral of a trouble condition. 
 
0
720 
Bypass Restore Report Code 
 
Enter the restore report code when the bypass of a zone is removed. 
 
0
730 
AC Loss Restore Report Code 
 
Enter the restore report code for a restoral of an ac loss condition. 
 
0
740 
Low Battery Restore Report Code 
 
Enter the restore report code for a restoral of a system low battery condition. 
 
0
750 
Charger Fail Report Code 
 
Enter the report code when the system detects a system battery’s charger 
circuit failure. 
NOTES: 
The system sends the Trouble Restore report code (field 71) upon restoral 
of the charger circuit. 
The system displays “CHARGER FAIL” when the system detects a system 
battery’s charger circuit failure. 
 
0
760 
Waterflow Alarm Silencing 
0 = silenced by User Code + OFF 
1 = silenced when zone restores 
Select how the Waterflow zone type will be silenced. 
NOTE: This feature may be set to 1 only by permission of the local authority. 
 
0
770 
Alarm Bell Sound 
0 = temporal pulse  
1 = steady 
Select the alarm output sounding. 
NOTE: For certain applications (ex. using a Sync module), a steady output 
must be selected. 
 
 
0
780 
Zone Types 17 & 18 Delay 
Enter 01-99 seconds 
Enter 
00 for no delay 
Select the delay time for zone types 17 and 18. The zone must be faulted for 
entire delay time before an alarm or supervisory condition occurs.  This may 
prevent alarms due to minor fluctuations in waterflow. 
NOTES:  
For type 18, enable the delay if field 57. 
The combined sensor and programmed delay must not exceed 90 seconds.