Fisher & Paykel 790 Active Smart - 10.12 Compressor Will Not Run And Is Hot To Touch; 10.13 Compressor Electrical Tests

Fisher & Paykel 790 Active Smart
59 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58
When defrost sensor
reaches +8 degrees C (46
degrees F) the compressor
will start
Has the
system gone
into defrost
mode?
Is current
being drawn
by defrost
element?
Yes
Check compressor
and system for
leaks/blockages and
repair as required
Yes
No
Remove FC cover.
Is there a full frost
pattern on the
evaporator?
Yes
10.12 Compressor Will Not Run And Is Hot To Touch
10.13 Compressor Electrical Tests
OK?
Refit original
electronic
module/inverter
Are
compressor
winding
resistances
OK?
OK?
Substitute
power/control
module
Yes
No
Replace
compressor
No
Are electrical
connections
to
compressor
OK?
Substiute electronic
module/inverter
Repair connections
OK?
Refit replacement
electronic
module/inverter
No
Yes
Yes
No
Problem solved
Yes
Yes

Table of Contents