EasyManua.ls Logo

Fluke 1663 - Page 54

Fluke 1663
99 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical Installation Tester
Measurements
45
4. Press to select the RCD test-current waveform:
E – AC current to test type AC (standard AC RCD) and type A
(pulse-DC sensitive RCD)
F – Half-wave current to test type A (pulse-DC sensitive RCD)
E G – Delayed response to test S-type AC (time delayed AC RCD)
F G – Delayed response to S-type A (time delayed pulse-DC
sensitive RCD)
1664 FC/1663
. – Smooth-DC current to test type B RCD
. G – Delayed response to S-type B (time delayed smooth-DC
current RCD)
Note
For type F, G, K or R RCDs, choose type A (half-wave current).
The symbol RCD is not triggered on the short delay of 10 ms
of the G, K, and R types. These types need a trip time of at
least 10 ms.
Type B+ RCDs are tested with type B smooth dc-current.
5. Press to select the test current phase, 0 ° or 180 °. RCDs should be
tested with both phase settings, as their response time can vary
significantly.
Note
For RCD type B (.) or S-type B (. G), you must test with
both phase settings.
6. At a minimum, connect the leads to L and PE of the system under test, or
plug the mains test cord into the socket under test.
Note
For RCD type B (.) or S-type B (. G) all three test leads
are required.
7. Press and release
.
If Auto Start (Power-on option: + up ) is turned on, the test starts
automatically as soon as the mains voltage is detected and the required
test leads are connected.

Table of Contents

Related product manuals