18-1
Chapter 18
Transients
Introduction
Fluke 435-II and 437-II can capture waveforms at high-resolution during a variety of
disturbances. The Analyzer will give a snapshot of the voltage and current waveforms at
the precise time of the disturbance. This allows you to see the waveforms during dips,
swells, interruptions, current swells and transients.
In Transients mode the Analyzer uses a special setting of its input circuit to allow
capturing signals up to 6 kilovolt in amplitude.
Transients are fast spikes on the voltage waveform. Transients can have so much energy
that sensitive electronic equipment can be affected or even damaged. The Transients
screen looks similar to that of Scope Waveform, but its vertical span is enlarged to make
voltage spikes visible that are superimposed on the 60 or 50 Hz sinewave. A waveform is
captured each time that the voltage (or rms current) exceeds adjustable limits. A
maximum of 9999 events can be captured. The sample rate for transient detection is
200 kS/s.
Transients also has a Meter mode showing half cycle rms for voltage (Vrms ½), current
(Arms ½), and frequency. Also an Events table is available.
1.800.868.7495info@Fluke-Direct.ca
Fluke-Direct.ca

Table of Contents

Other manuals for Fluke 434-II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fluke 434-II and is the answer not in the manual?

Fluke 434-II Specifications

General IconGeneral
BrandFluke
Model434-II
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals