- Wait for one minute, grid may go back to normal working state.
- Make sure that grid voltage and frequency complies with standards.
- Or, please seek for help from us.
- Disconnect PV (+), PV (-) with DC.
- After the LCD switches off, reconnect and check again.
- Please seek for help from us if it cannot go back to normal state.
- Check the impedance among PV (+), PV (-) and ground. Impedance
should be >1Mohm.
- Please seek for help from us if it cannot be detected or the impedance is
<1Mohm.
- Check the voltage of neutral and PE.
- Check AC wiring.
- Restart inverter, if error message persists, seek for help from us.
- Turn off the PV and grid, reconnect them.
- Or seek for help from us if it does not go back to normal.
- System will reconnect if the utility is back to normal.
- Or seek for help from us if it does not go back to normal state.
- Check the panel’s open-circuit voltage whether the value is similar or
already >550Vdc.
- Please seek help from us when voltage ≤550Vdc.
- Disconnect PV (+), PV (-) with DC.
- After the LCD switches off, reconnect and check again.
- Please seek for help from us if it does not go back to normal state.
- Disconnect PV (+), PV (-) with DC.
- After the LCD switches off, reconnect and check again.
- Please seek for help from us if it cannot go back to normal state.
- Disconnect PV+, PV-, reconnect them.
- Or seek for help from us if it does not go back to normal state.
- Disconnect PV (+), PV (-) with DC.
- After the LCD switches off, reconnect and check again.
- Please seek for help from us if it cannot go back to normal state.
- Check if the environment temperature is over the limit.
- Or seek for help from us.