16
FREQUENCIES
NEF67TM7
The frequencies indicated below take into account factors of use of
different engine uses; the most suitable duration of the maintenance
intervals for the different applications will be indicated by the
maintenance personnel based on the use and operating conditions of
the engine.
Do not perform maintenance in the case of live
electrical voltage: check the condition of the
equipment's ground connection. During the diagnostics
and maintenance operations, make sure your hands
and feet are dry and use insulating footboards if
possible.
The conditions that cause an emergency generator set
to start can occur suddenly. While performing checks
and maintenance, comply strictly with the
requirements indicated by the Manufacturer of the
generator set and by the Fitter of the electric
generation system to ensure maximum safety for
maintenance personnel.
Checks in periods of use Frequency
Check the engine lubricant oil level Daily
Check engine coolant level Daily
Check the cleanliness of the heat exchanger
(radiator)
Daily
Inspection of the exhaust duct/s Daily
Inspection of air filter Monthly
(2)
Check tightening and cleanliness of battery
clamps
Six-months
Check electrolyte level of the batteries Six-months
Check condition of the blow-by filter Six-months