EasyManua.ls Logo

Friedrich MR30C3F - Specifications and Electrical Data; Electrical Data Overview; Compressor Specifications; Fan Motor Performance

Friedrich MR30C3F
27 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12006.03.15
SPECIFICATIONS
INDOOR UNIT
MW30C3F
OUTDOOR UNIT
MR30C3F
COOLING CAPACITY
30,700 BTU/hr
POWER SOURCE
208 V / 230 V
FREQUENCY
60 Hz
RUNNING CURRENT
15.2 A
INPUT WATTS
3,460 W
SEER
15.0
MOISTURE REMOVAL
9.7 Pts/hr (4.6 L/hr)
AIR CIRCULATION-High
647 cfm (1,100 m
3
/hr)
ELECTRICAL DATA
COMPRESSOR
FAN MOTOR
DIMENSIONS
TYPE
Hermetic motor compressor,
4 poles, Rotary type
DISCRIMINATION
POWER SOURCE
5KD240XAD21
208 V / 230 V 60Hz
REFRIGERANT
R-410A
4 lb.10 oz ( 2,100 g )
POWER SOURCE
208 V / 230 V
HIGH
1,330 r.p.m.
1,120 r.p.m.
940 r.p.m.
830 r.p.m.
850 r.p.m.
INDOOR UNIT
MED
LO W
QUIET
OUTDOOR UNIT
INDOOR UNIT
HxWxD
HxWxD
12-5/8 x 39-1/4 x 9 inch
OUTDOOR UNIT
NOISE LEVEL
HIGH
47 dB
41 dB
36 dB
32 dB
53 dB
INDOOR UNIT
MED
LO W
QUIET
OUTDOOR UNIT
REFRIGERANT CHARGE (R410A)
20 m
4 lb. 10 oz. (2,100 g)
5 lb. 8 oz. (2,500 g)
6 lb. 6 oz. (2,900 g)
7 lb. 4 oz. (3,300 g)
40 g/m
FULL CHARGE
Pipe length
30 m
40 m
50 m
ADDITIONAL CHARGE
WEIGHT
INDOOR UNIT Gross / Net
Gross / Net
40 / 31 lbs. (18 / 14 kg )
OUTDOOR UNIT
155 / 137 lbs. (70 / 62 kg )
320 x 998 x 228 mm
32-3/4 x 35-3/8 x 13 inch
830 x 900 x 300 mm

Related product manuals