Frigomatic Milano Manual v1 PAGE 10
When all connections are completed, operate the water pump independently and make
sure that:
A.- You have no water leaks.
B.- The water flow is at least 1/2 gall/min (2 l/min).
4.3 - PUMP SPECIFICATION
The pump we supply with the unit is A092819C or PF-1A092819C
It must have a 12V supply (see wiring diagrams for details)
For 24V applications the pump is the same but it needs a pump interface (E51385), which
halves the voltage (from 24V to 12V). Note that this can also be used to run up to 3x water
cooled compressors from the same pump.
4.4 ALTERNATIVE PUMPS
Any pump can be used to circulate water through the Milano water cooled condenser as
long as:
A.- The water flow is at least 0,5 gal/min (2 l/min) and does not exceed 10 litres per minute
B.- A relay is always used to operate the pump.
C.- The pump is suitable for continuous duty.