AC input/output data
Maximum output fault current / dura-
tion
29 A / 3 ms
AC output data PV Point
Max. output power 4133 W (for 5 s)
Rated power 3000 W
Nominal output current 13 A
Nominal grid voltage 1 ~ NPE 220 V / 230 V / 240 V
Nominal frequency
53 / 63 Hz
1)
Switchover time < 90 s
Power factor cos phi
2)
0-1
AC output data Full Backup
Max. output power 13,780 W (for 5 s)
Rated power 10,000 W
Nominal output current 43.5 A
Nominal grid voltage
1 ~ NPE 220 V
1 ~ NPE 230 V
1 ~ NPE 240 V
Nominal frequency for Full Backup
53 / 63 Hz
1)
Switchover time < 90 s
Power factor cos phi
2)
0-1
General data
Maximum efficiency 97.3%
European efficiency (U
mpp nom
) 97%
European efficiency (U
mpp max
) 96.5%
European efficiency (U
mpp min
) 96.6%
Self-consumption at night 9 W
Cooling Controlled forced-air ventilation
Protection class IP 66
Dimensions H x W x D 595 × 529 × 180 mm
Weight 23.5 kg
Inverter topology Non-insulated transformerless
Permitted ambient temperature -40 °C – +60 °C
Permissible humidity 0-100% (incl. condensation)
EMC emission class B
DC/AC overvoltage category
(in accordance with IEC 62109-1)
2/3
Pollution degree 2
171